Gas Monitoring System / Sampling System
>> PRODUCT MAKER :    
 
Model : PGS32
 
● Programmable gas sampling system
● PC로 system configuration anc control
● 하나의 캐비넷으로 32개의 sample points를 자동으로 모니터링
● Pellistor, Electrochemical, Thermal conductivity, Semiconductor 또는 Infrared Detector 를 센서 종류에 상관없이 8개까지 연결 가능
● Automatic data logging
     
 
 
* Sampling System
. Sample lines : 10mm od, 8mm id, reinforced nylon, polypropylene or HDPE(PTFE or PVDF for reactive gases), installed in plastic or metallic conduit for physical protection.

. Max. line length : Up to 1km

. Exhausts : 6mm od compression fitting

. Drains : 10mm od compression fitting

. Flashback arrestores : 90µ, 1.6mm thick, 303 stainless steel

* Cabinet
. Overall dimensions : Top cabinet ; 380 x 600 x 350 mm ; Bottom cabinet ; 760 x 600 x 350 mm

. Weigt : 70kg

. Temperature range : 10 to 25℃

* Electrical
. Power : 110 or 230V ac 50/60Hz

. Inputs/Outputs : Any combination of relay and analogue modules, up to a maximum of 4 modules.
Relay modules contain 8 output relays - 4 x SPCO 10A and 4 x DPCO 5A. All contacts rated at 250V, non-inductive load.
Analogue modules contain 8 inputs and 2 outputs, all 4-20mA, rated 800 ohms max. load at 24V dc.