Model : TP-P-48-N-NDI
 
Surge Protection
¡Ü Çʵå ÄÉÀÌºí¸µ¿¡¼­ ½áÁö¿Í °úµµ»óŸ¦ ´ëºñÇÑ ÀüÀÚ Ã³¸® Æ®·£½º¹ÌÅÍ º¸È£ÀåÄ¡
¡Ü ½±°í °£´ÜÇÑ ¸¶¿îÆÃ

¡Ü Intrinsically safe & flameproof
¡Ü loopÀÇ ½ÅÈ£ÀúÇϸ¦ ¸·±â À§ÇÑ ³·Àº impedanceÀÇ Á÷·Ä¿¬°á
¡Ü ATEX ¿Í FM °ËÁõ
¡Ü Á¦Ç°º¸Áõ±â°£ 10³â
     
 
 
All figures typical at 77¡ÆF (25¡ÆC) unless otherwise stated

Maximum surge current : 20kA peak current (8/20¥ìs waveform)

Leakage current : Less than 10¥ìA at max. working voltage

Working voltage : 48V dc and 32V dc maximum

Bandwidth : 1MHz

Resistance : Loop resistance: 1ohm

Ambient temperature limits : -40¡ÆC to +85¡ÆC (-40¡ÆF to +185¡ÆF) (working)
-40¡ÆC to +85¡ÆC (-40¡ÆF to +185¡ÆF) (storage)

Humidity : 5% to 95% RH (non-condensing)

Electrical connections
Input: 3 position socket/header (max wire#14AWG (2mm2)
Output: 3 flying leads (line 1, line 2 & earth)Wire size 32/0.2 (1.0mm2, 18AWG) Lead length 250mm (9.85¡±) minimum

Casing : ANSI 316 stainless steel hexagonal barstock,male and female thread

Weight : 175g (6.2oz.)

EMC compliance : To Generic Immunity Standards BS EN 61326-1:2006 for industrial environments

Hazardous area connections :
Ex ia IIC T4, Ceq=O, Leq=0; the unit can be connected without further certification
into any intrinsically safe loop with open circuit voltage <60V and input power <1.2W.
Ex d IIC T4; the unit is apparatus-approved to flameproof (explosionproof) standards, and can be fitted into a similarly approved housing.