Pressure Measurement System / Pressure Sensors
>> PRODUCT MAKER :    
 
Model : FCO53
 
»ê¾÷¿ë Â÷¾ÐÆ®·£½º¹ÌÅÍ
FCO53Àº transformer, power supply transducer¿Í ±â´É board·Î ¸¸µé¾îÁø »ê¾÷¿ë Â÷¾ÐÆ®·£½º¹ÌÅÍÀÌ´Ù.

¡¤ 1~2000mmH2O
¡¤ IP65 ¹æ¼ö ¾ß±Ý ÄÉÀ̽º¡¤230V ac 110V ac ¶Ç´Â 24V dc 3, 4wire
¡¤ 4~20mA¶Ç´Â 0~10V dc
¡¤ standard type: 303 stainless steel, brass, nitrile ¡®O¡¯ rings, silicon grease nylon tubing
 Corrosion-resistant type: 316 stainless steel, PTFE
¡¤ 100:1 overload factor
¡¤ ¾ÆÁÖÀÛÀº gas volume ¿ä±¸
¡¤ ¶ß°Ì°í ´õ·¯¿î °ø±â³ª °¡½º À¯µ¿¿¡ ÀûÇÕ.
     
 
 
. Pressure media : Air and gases
. Accuracy : ¡¾0.5% FSD including effects of linearity and hysteresis
. Overpressure : 100 times differential pressure range (10,000%)
. Resolution : 0.1% of full scale output
. Response time for step change : 20ms to 10s fully adjustable
. Instrument temperature limits : -20 to +60¡É
. Gas temperatures at source : Any
. Compensated temperature range : 10 to 30¡É
. Temperature coefficient on zero : 0.4% per 10¡É
. Temperature coefficient on span : 0.5% per 10¡É
. Warm up period : 1 hour
. Long term drift at constant temperature : ¡¾1% maximum diviation
. Static working pressures : 0 to 11 bars absolute
. Zero offset : ¡¾20%
. Span adjust : 50 to 150% of calibrated range
. Tilt effect (worst case) : 1% of 90¢ª
. Vibration across diaphragm plane per 1g : 0.1% typical
. Volumetric displacement : 0.003§¨ for full scale
. Relative humidity of gas source : max. 95% RH non-condensing
. Input : 110V ac, 230V ac, 24V dc
. Weight : 3kg
. Dimensions : 220(w) x 120(h) x 84(d) mm

* Outputs (all fully floating)
1. 0 to 10mV impedance min. load 10R
2. 0 to 1V dc impedance min. load 200R
3. 0 to 10V dc impedance min. load 1K
4. 0 to 1mA impedance max load 5K
5. 0 to 10mA impedance max. load 1K
6. 4 to 20mA impedance max. load 500R